Load & Backup Requirements
Battery System
Battery Bank Required
A simple calculation might suggest that running a 1,000 W AC for 4 hours needs 4 kWh of battery. In practice you always need more, for three reasons: the depth of discharge limit means you cannot use all the energy stored; the inverter wastes some energy in conversion; and battery internal resistance under load also takes a small share. Together these factors mean the bank must hold 20 to 80% more than the bare load calculation, depending on battery type and inverter quality.
| Type | Usable DOD | Cycle life | Best for AC backup? |
|---|---|---|---|
| Lead-acid (FLA / AGM) | 50% | 300 to 500 cycles | Low cost but heavy, needs twice the capacity |
| LiFePO4 (lithium iron) | 80% | 2,000 to 6,000 cycles | Best choice for AC backup |
| NMC lithium (phone / laptop type) | 80 to 90% | 500 to 1,000 cycles | Not recommended for high-current AC loads |
| Voltage | Current for 1,000 W load | Cable size needed | Verdict |
|---|---|---|---|
| 12 V | ~83 A | Very large (35 to 50 mm²) | Impractical for AC loads |
| 24 V | ~42 A | Large (16 to 25 mm²) | Workable for small systems |
| 48 V | ~21 A | Manageable (6 to 10 mm²) | Recommended for AC backup |
A 1,000 W inverter AC plus 200 W of fans and lights for 4 hours. LiFePO4 batteries at 48 V, 100 Ah each, 90% efficient inverter.
How many batteries for a 1.5 ton AC?
For 4 hours at 1,000 W: about 4.4 kWh lithium or 8.9 kWh lead-acid total capacity. In a 48 V system: 2 LiFePO4 modules at 100 Ah each. In a 12 V lead-acid system: roughly 7 to 8 batteries of 100 Ah each.
What is depth of discharge?
The percentage of total capacity you can safely use. Lead-acid: 50% max. LiFePO4 lithium: 80 to 90%. Using more than the rated DOD dramatically shortens battery life.
Why do I need more battery than the load calculation suggests?
Three losses reduce usable energy: DOD limit, inverter conversion loss, and battery internal resistance. Together they mean the bank must hold 20 to 80% more than the bare watt-hour calculation.
How long can a battery backup run an AC?
Usable battery kWh divided by AC load in kW. A 10 kWh usable bank running a 1 kW AC lasts about 10 hours in isolation, less when sharing with other loads.
Lead-acid or lithium for AC backup?
LiFePO4 lithium is strongly preferred: 80% usable DOD vs 50% for lead-acid, 3 to 5 times more cycle life, and better performance under the high continuous current that an AC demands.
What system voltage for AC backup?
48 V is recommended. At 12 V the currents for a 1,000 W load reach 83 A, requiring very thick cables. At 48 V the current drops to about 21 A, making the system safe and practical.
Capacity figures are calculated from the parameters you enter. Actual battery performance varies with temperature, age and discharge rate. Add a real-world margin above the calculated figure.