System Details
Duct Sizing Results
CFM, cubic feet per minute, is the volume of air an HVAC system moves per minute. Getting CFM and duct size right matters as much as choosing the correct AC tonnage. An undersized duct creates excess pressure, noise, and turbulence. An oversized duct moves air too slowly, reducing its ability to mix with room air and deliver effective cooling. The goal is a duct system where every register delivers the right CFM at a comfortable velocity.
| AC Size | Total CFM (standard 400/ton) | At 350 CFM/ton (high humidity) | At 450 CFM/ton (low humidity) |
|---|---|---|---|
| 0.75 ton | 300 CFM | 263 CFM | 338 CFM |
| 1 ton | 400 CFM | 350 CFM | 450 CFM |
| 1.5 ton | 600 CFM | 525 CFM | 675 CFM |
| 2 ton | 800 CFM | 700 CFM | 900 CFM |
| 2.5 ton | 1,000 CFM | 875 CFM | 1,125 CFM |
| 3 ton | 1,200 CFM | 1,050 CFM | 1,350 CFM |
| CFM | At 500 FPM | At 700 FPM | At 900 FPM |
|---|---|---|---|
| 100 CFM | 6.8 in / 173 mm | 5.7 in / 145 mm | 5.0 in / 127 mm |
| 200 CFM | 9.6 in / 244 mm | 8.1 in / 206 mm | 7.1 in / 180 mm |
| 400 CFM | 13.5 in / 343 mm | 11.4 in / 290 mm | 10.1 in / 257 mm |
| 600 CFM | 16.6 in / 422 mm | 14.0 in / 356 mm | 12.3 in / 312 mm |
| 800 CFM | 19.1 in / 485 mm | 16.1 in / 409 mm | 14.3 in / 363 mm |
| 1,000 CFM | 21.4 in / 543 mm | 18.0 in / 457 mm | 16.0 in / 406 mm |
Return ducts carry room air back to the AC unit and operate at lower velocity than supply ducts. A common design practice: size return ducts for 400 to 600 FPM using the same total CFM as the supply system. Return ducts are therefore typically one to two sizes larger than their corresponding supply duct. A system with 600 CFM supply at 700 FPM (14-inch round) would need a 16 to 18 inch return duct at 400 to 500 FPM.
In mini-split split AC systems (common in Asia, Europe, and many residential applications), ducting is typically not used, the indoor unit blows directly into the room. This calculator primarily applies to ducted central air systems and is most relevant for North American, Australian, and Middle Eastern whole-home HVAC systems.
A 2 ton central AC feeds 4 supply registers across a small apartment. Target velocity is standard residential (700 FPM). Using round duct:
If flexible duct is used instead of rigid metal, increase each diameter by roughly one size to compensate for the higher friction of the corrugated interior surface.
How much CFM do I need per ton?
400 CFM per ton is the standard residential benchmark. A 1.5 ton AC needs 600 CFM total. In high-humidity climates, 350 CFM/ton improves dehumidification by extending air contact time with the coil.
What is the correct duct velocity?
Supply main: 600 to 900 FPM. Branch to bedroom: 400 to 700 FPM. Return: 400 to 600 FPM. Lower velocities reduce noise; higher velocities allow smaller ducts but increase noise and pressure drop.
What round duct for 600 CFM?
At 700 FPM: approximately 14 inches (356 mm). At 600 FPM: approximately 15.2 inches. At 900 FPM: approximately 12.3 inches.
Does duct length affect sizing?
Yes. Runs above 50 ft (15 m) should be sized one diameter larger to compensate for friction losses. Each 90-degree elbow adds ~10 ft of equivalent straight-duct friction.
What is the difference between supply and return ducts?
Supply ducts carry cooled air to rooms at 600 to 900 FPM. Return ducts bring room air back to the unit at 400 to 600 FPM and are therefore typically one to two sizes larger than the supply for the same CFM.
Does this apply to mini-split AC systems?
Mini-split wall-mounted units (standard in Asia, Europe, and many residential markets) do not use ductwork, the indoor unit blows directly into the room. This calculator applies to ducted central air systems.
Duct sizing results are estimates based on standard residential HVAC design rules. For complex systems, high-rise buildings, or commercial installations, consult a licensed HVAC engineer.